/Products/Surplus Industrial/Fire Protection Equipment/5110XM-9 Honeywell Fire Sprinkler Alarm Control
Click Image to Expand

Product ID: 5110XM-9

5110XM-9 Honeywell Fire Sprinkler Alarm Control

MFG: Honeywell International, Inc
MFG Part Number: 5110XM-9

Selected accessories will also be added to cart
$499.97 / Each
Quantity:
New, Surplus Stock
Available Stock: 1
The 5110XM is a fire alarm control/communicator that supports five hardwired zones. It may be used as a fire detection system or a slave Digital Alarm Communicator Transmitter (DACT), providing central or remote station service for a central or remote station listed Fire Alarm Control Panel (FACP). It may also be used as a standalone non-coded local, central station or remote station control.
The model 5110XM is fully supervised and supports one two-wire smoke detection circuit and four-wire smoke detectors on all five circuits. Its microprocessor continuously monitors and reports system status of AC, standby battery, zone inputs and telephone line connections. In the event of a fault condition, a local audible sound is activated and a report is sent directly to the central station.

Features:
• Five supervised style B zones
• One master code
• Five user codes
• Seven built-in LED indicators
• One notification appliance circuit
• Temporal code compliant
• Supervised digital dialer
• Optional panel door mounted silence/reset switch when AHJ approved
• Supports two-wire compatible smoke detector
• Supports up to four keypads
• Backup digital dialer built in
• Auxiliary form “C” relay
• Built-in warning buzzer Programmable via 6160 alpha keypad or downloader
• Supports major communication formats
• ETL Listed to UL864 9th Edition
• NFPA 72 compliant
• MEA Approved
• Upload/download capable

Electrical Specifications:
Primary power
• 20VAC, 60 Hz, 600mA max
• Secondary rated 18VAC, 40VA
Quiescent panel current draw
• 155mA
Backup battery
• 12VDC, 7AH min to 14AH max
• Lead acid battery (gel type)
Charging voltage
• 1 3.7VDC, nominal
Alarm power
• 12VDC, 1.0A max for notification (bell) output
Aux. standby power
• 12VDC, 350mA max
Total power
• 1.0A from all sources
Aux. relay output
• Type: Form C
Standby time
• 24 hours with 1A standby load or 60 hours with 210mA max standby load using 14AH battery
Fusing
• Battery input, aux. and notification (bell) appliance circuits are protected using PTC circuit protectors. All outputs are power limited.
Dialers Line seize
• Double Pole
Ringer equiv.
• 0.7B
Formats
• Honeywell Low Speed, Honeywell 4+2 Express, Honeywell High Speed, Honeywell Contact ID, Sescoa and Radionics

Cabinet dimensions
• 14.5" H X 1 2.5" W X 3" D
Environmental
• 14° F to 158° F (-10° C to 70° C)
Operating temp
• 32° F to 122° F (0° C to 50° C)
Humidity
• 85% RH
EMI
• Meets or exceeds the following
requirements:
• FCC Part 15, Class B Device
• FCC Part 68
• IEC EMC Directive