/Products/Electric Motors/3 Phase/WEG/Super Premium Efficiency/04018EG3E324T-W22 WEG 40HP Electric Motor, 1800RPM

Product ID: 04018EG3E324T-W22

04018EG3E324T-W22 WEG 40HP Electric Motor, 1800RPM

MFG: WEG Electric Corporation
MFG Part Number: 04018EG3E324T-W22

Selected accessories will also be added to cart
$3,447.00 / Each
Quantity:
IC411 - TEFC, IP55, 324T/326T Frame, 208-230/460/380VAC 50/60Hz 3 Phase, 12604500, Super Premium Efficiency, Foot Mounted, Cast Iron Frame, 2-1/8" Keyed Shaft

Electric Motors

Frame 324/6T
Output 40 HP (30 kW)
Number of Poles 4
Frequency 60 Hz
Rated speed 1780 rpm
Slip 1.11 %
Rated voltage 230/460 V
Rated current 97.8/48.9 A
L. R. Amperes 822/411 A
LRC 8.4x(Code K)
No load current 44.0/22.0 A
Rated torque 118 ft.lb
Locked rotor torque 320 %
Breakdown torque 350 %
Locked rotor time 39s (cold) 22s (hot)
Moment of inertia (J) 8.83 sq.ft.lb
Design A
Insulation Class F
Service factor 1.25
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 66.0 dB(A)
Approx. weight³ 599 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
93.6  94.5  95.0 

Power factor

50% 75% 100%
0.64  0.75  0.81 
Frame 324/6T
Output 40 HP (30 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1475 rpm
Slip 1.67 %
Rated voltage 380 V
Rated current 57.7 A
L. R. Amperes 364 A
LRC 6.3x(Code G)
No load current 22.0 A
Rated torque 142 ft.lb
Locked rotor torque 250 %
Breakdown torque 270 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 8.83 sq.ft.lb
Design A
Insulation Class F
Service factor 1.25
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 63.0 dB(A)
Approx. weight³ 599 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
93.6  94.1  94.1 

Power factor

50% 75% 100%
0.70  0.80  0.84 
Frame 324/6T
Output 40 HP (30 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1480 rpm
Slip 1.33 %
Rated voltage 400 V
Rated current 55.2 A
L. R. Amperes 403 A
LRC 7.3x(Code H)
No load current 23.5 A
Rated torque 142 ft.lb
Locked rotor torque 280 %
Breakdown torque 310 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 8.83 sq.ft.lb
Design A
Insulation Class F
Service factor 1.15
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 63.0 dB(A)
Approx. weight³ 599 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
94.1  94.5  94.5 

Power factor

50% 75% 100%
0.66  0.77  0.83 
Frame 324/6T
Output 40 HP (30 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1480 rpm
Slip 1.33 %
Rated voltage 415 V
Rated current 54.5 A
L. R. Amperes 452 A
LRC 8.3x(Code K)
No load current 25.0 A
Rated torque 142 ft.lb
Locked rotor torque 300 %
Breakdown torque 330 %
Locked rotor time 32s (cold) 18s (hot)
Moment of inertia (J) 8.83 sq.ft.lb
Design A
Insulation Class F
Service factor 1.15
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 63.0 dB(A)
Approx. weight³ 599 lb
(1) Looking the motor from the shaft end.; (2) Measured at 1m and with tolerance of +3dB(A).; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
94.1  94.5  94.5 

Power factor

50% 75% 100%
0.63  0.75  0.81 

Features

Frame Material Cast Iron 
Impregnation Method Dip and Bake Polyester 
Regreasing System At Drive end and Non-drive end 
Main terminal box hole NPT 2" 
Terminal Block Without 
Shaft Locking Device Without 
Drain Rubber, automatic 
Shaft Material SAE 1040/45 Carbon Steel 
Painting RAL 6002 203A (ISO 12944 - C2) 
Grounding Lugs Single 
Fan Cover material Cast Iron 
Tropicalized Painting Without 
Fan material Plastic 
Bearing cap Yes- Bearing Cap 
Balancing Method 1/2 Key 
Drip Cover Without 
Overload protector (phenolic) Without overload protector  
Connection Cables Quantity 12