IC01 - ODP, IP23, 324TC/326TC Frame, 230/460/380VAC 50/60Hz 3 Phase, 14491997, High Effiency, Foot Mounted, C-Face, Cast Iron Frame, 2-1/8" Keyed Shaft

Electric Motors

Frame 324/6TC
Output 50 HP (37 kW)
Number of Poles 4
Frequency 60 Hz
Rated speed 1775 rpm
Slip 1.39 %
Rated voltage 230/460 V
Rated current 120/60.2 A
L. R. Amperes 722/361 A
LRC 6.0x(Code G)
No load current 53.6/26.8 A
Rated torque 148 ft.lb
Locked rotor torque 240 %
Breakdown torque 229 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 5.98 sq.ft.lb
Design B
Insulation Class F
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 520 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
92.4  93.0  93.0 

Power factor

50% 75% 100%
0.67  0.78  0.83 
Frame 324/6TC
Output 40 HP (30 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1475 rpm
Slip 1.67 %
Rated voltage 380 V
Rated current 59.5 A
L. R. Amperes 375 A
LRC 6.3x(Code G)
No load current 26.1 A
Rated torque 142 ft.lb
Locked rotor torque 220 %
Breakdown torque 229 %
Locked rotor time 23s (cold) 13s (hot)
Moment of inertia (J) 5.98 sq.ft.lb
Design B
Insulation Class F
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP23
Enclosure IC01 - ODP
Mounting F-1
Rotation¹ Both (CW and CCW)
Approx. weight³ 520 lb
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.

Efficiency

50% 75% 100%
91.7  92.4  92.3 

Power factor

50% 75% 100%
0.67  0.78  0.83 

Features

Frame Material Cast Iron 
Impregnation Method Dip and Bake Polyester 
Regreasing System At Drive end and Non-drive end 
Main terminal box hole NPT 2" 
Terminal Block Without 
Shaft Locking Device Without 
Shaft Material SAE 1040/45 Carbon Steel 
Painting RAL 3002 203A (ISO 12944 - C2) 
Grounding Lugs Single 
Fan Cover material Without Fan Cover 
Tropicalized Painting Without 
Fan material Without fan 
Bearing cap Yes- Bearing Cap 
Bolt Material Carbon Steel 
Balancing Method 1/2 Key 
Drip Cover Without 
Overload protector (phenolic) Without overload protector  
Connection Cables Quantity 12